TUV Enclosed Busduct GFM Non Segregated Busway
product detail
TUV Enclosed Busduct GFM Non Segregated Busway
Descriptionm
Rated Current: | 630A--6300A | Frequency: | 50Hz/60Hz |
Rated Voltage: | 3.6-40.5KV | IP: | IP54 |
Product Series: | Nonsegregated Busduct/ Segregated Phase Busduct | Design Criteria: | GB/T 8349 |
Product Type: | TMY/LMY | ||
High Light: | UL TUV non segregated busway, GFM Enclosed Busduct, ASTA non segregated busway |
GFM non - segregated busway,Enclosed busduct
GFM Series non-segregated phase busway is suitable for transmission system, which provides consistent strength and high short-circuit ratings.
The busduct is outfitted with ancillary cabinets that includes a voltage transformer, lightning arrester, excitation cubicle, neutral grounding resistor, busbar current transformer and other components.
Standards | IEC364-5-54/GB/T8349-2000/JB/T9639-1999 | ||||
Ambient | ℃ | ||||
Relative humidity | Daily averages ≤ 95%. Monthly average ≤ 90% | ||||
IP | IP40, IP54 | ||||
Rated voltage | kV | 3.15 | 6.3 | 10.5 | 35 |
Max operating voltage | kV | 3.6 | 7.2 | 12 | 40.5 |
Insulation level | kV | 25/40 | 32/60 | 42/75 | 100/185 |
Rated frequency | Hz | 50(60) | |||
Rated operating current | Dimension (W×H)(mm×mm) | ||||
1000-3000 | A | I 750×400 II 850×350 | I 900×560 II 1060×460 | I 900×560 II 1060×460 | I 1500×920 II 1800×880 |
3500 | A | I 750×440 II 850×480 | I 900×560 II 1060×460 | I 900×560 II 1060×460 | |
4000 | A | I 750×440 II 850×480 | I 900×560 II 1060×460 | I 900×560 II 1060×460 | |
4500 | A | I 750×440 | I 1000×560 | I 1000×560 | |
5000 | A | I 1350×500 | I 1500×600 | I 1500×600 | |
6300-6800 | A | I 1350×500 | I 1500×600 | I 1500×600 |