Leave Your Message
QBJGM Insulated Pipe 630A Medium Voltage Busway
Medium Voltage Busway

QBJGM Insulated Pipe 630A Medium Voltage Busway

Product Details:

Place of Origin: CHINA
Certification: KEMA,ASTA,CE,GOST-R,CEDIT,TUV
Model Number: Q(B)JGM

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Price: Negotiable
Packaging Details: Standard package
Delivery Time: 20 working days after confirmation of all technical data and advance payment
Supply Ability: 300 Pieces per Month

    product detail

    QBJGM Insulated Pipe 630A Medium Voltage Busway

    Description

    Conductor Type: Cu Pipe / Al Pipe Rated Current: 630A--6300A
    Frequency: 50Hz/60Hz Rated Voltage: 3.6-40.5KV
    IP: IP65 Product Series: Semic Insulated / Insulated
    Design Criteria: DL 1658 AND GB/T 8349 Product Type: Insulate Pipe Busduct
    High Light:     630A Medium Voltage Busway, 630A Insulate pipe busduct, KEMA Medium Voltage Busway

    Q ( B ) JGM insulated pipe busway , 630A - 6300A

     

    GFM series bus ducts supply consistent strength and low short-circuit ratings. Protected by aluminum or low magnetic plate enclosures, no hysteresis loss occurs on the distribution system. The housing experiences low temperature increases, reducing energy loss on the entire system.

    Standards IEC364-5-54/GB/T8349-2000/JB/T9639-1999
    Ambient  
    Relative humidity   Daily averages ≤ 95%. Monthly average ≤ 90%
    IP   IP40, IP54
    Rated voltage kV 3.15 6.3 10.5 35
    Max operating voltage kV 3.6 7.2 12 40.5
    Insulation level kV 25/40 32/60 42/75 100/185
    Rated frequency Hz 50(60)
    Rated operating current   Dimension (W×H)(mm×mm)
    1000-3000 A I 750×400 II 850×350 I 900×560 II 1060×460 I 900×560 II 1060×460 I 1500×920 II 1800×880
    3500 A I 750×440 II 850×480 I 900×560 II 1060×460 I 900×560 II 1060×460  
    4000 A I 750×440 II 850×480 I 900×560 II 1060×460 I 900×560 II 1060×460  
    4500 A I 750×440 I 1000×560 I 1000×560  
    5000 A I 1350×500 I 1500×600 I 1500×600  
    6300-6800 A I 1350×500 I 1500×600 I 1500×600  

    Q(B)JGM Insulation pipe busway is with tubular conductor. The inside diameter air channel can form hot air convection naturally with good dissipation (the pressure difference between indoor and outdoor can form hot air convection naturally).