The refractory busway is suitable for three-phase four-wire and three-phase five-wire supply and distribution systems with AC 50~60Hz, voltage 660V and below, rated current 250~3150A with high fire protection requirements. The product is made of insulating material with high temperature resistance above 500℃, while the heat insulation layer is made of heat insulation and temperature resistant material above 1000℃, and the shell is made of steel. The fire-resistant busway has passed the 950°C, 90-minute to 3-hour high-temperature fire test, as well as the full-load current-carrying test and the waterproof test, and the full set of standard tests for busways, so the selection of this busway can ensure the current-carrying capacity and the stability of power supply for fire-fighting equipment. This series of products can maintain power supply for a certain period of time in case of fire to ensure enough time to start fire-fighting equipment, smoke exhaust and ventilation, and evacuate people.

    Product Parameters


    Executive standard

    IEC61439-6,GB7251.1,HB7251.6

    System

    Three-phase three-wire, three-phase four-wire, three-phase five-wire, three-phase five-wire (shell as PE)

    Rated frequency f (Hz)

    50/60

    Rated insulation voltage Ui (V)

    1000

    Rated working voltage Ue (V)

    380-690

    current (A)

    250A~6300


    Product Technical Parameters


    1. NHCCX series busways are in compliance with IEC60439-1~2, GB7251.1-2, JISC8364, GB9978 standards for each performance.
    2. The busway can withstand 2500V frequency withstand voltage for 1min without breakdown and flashover.
    3. The busway is able to withstand strong electric and thermal stresses due to the use of high-strength ceramic as the phase separation material. According to the data in Table (2), the busways passed the dynamic and thermal stability test and showed undetectable ^ deformation after the test.


    Rated working current(A)

    250

    400

    630

    800

    1000

    1250

    1600

    2000

    2500

    3150

    Short-time withstand current(A)

    10

    15

    20

    30

    30

    40

    40

    50

    60

    75

    Peak withstand current(A)

    17

    30

    40

    63

    63

    84

    84

    105

    132

    165


    The temperature rise of the conductive parts of the busway trough does not exceed the values listed

    in the following table when the rated current is passed for a long time

    conductive part

    Maximum allowable temperature rise(K)

    connection terminals

    60

    Housing

    30




    Product Selection Table


    Current level(A)

    Name

    NHKMC1 Fire-resistant busway/4P

    NHKMC1 Fire-resistant busway/5P

    Dimension

    Wide(mm)

    High(mm)

    Wide(mm)

    High(mm)

    250A

    192

    166

    213

    166

    400A

    192

    176

    213

    176

    630A

    195

    176

    213

    176

    800A

    195

    196

    213

    196

    1000A

    195

    206

    213

    206

    1250A

    195

    236

    213

    236

    1600A

    208

    226

    232

    226

    2000A

    208

    246

    232

    246

    2500A

    224

    276

    250

    276

    3150A

    224

    306

    250

    306


    Current level(A)

    Name

    NHCCX Fire-resistant busway/4P

    NHCCX Fire-resistant busway/5P

    Dimension

    Wide(mm)

    High(mm)

    Wide(mm)

    High(mm)

    250A

    240

    180

    261

    180

    400A

    240

    180

    261

    190

    630A

    243

    190

    261

    190

    800A

    243

    210

    261

    210

    1000A

    243

    220

    261

    220

    1250A

    243

    250

    261

    250

    1600A

    256

    258

    280

    258

    2000A

    256

    278

    280

    278

    2500A

    272

    308

    298

    308

    3150A

    272

    338

    298

    338


    Current level(A)

    Name

    NHKMC2 Fire-resistant busway/4P

    NHKMC2 Fire-resistant busway/5P

    Dimension

    Wide(mm)

    High(mm)

    Wide(mm)

    High(mm)

    250A

    161

    128

    164

    128

    400A

    161

    138

    164

    138

    630A

    161

    148

    164

    148

    800A

    161

    158

    164

    158

    1000A

    161

    178

    164

    178

    1250A

    161

    208

    164

    208

    1600A

    161

    248

    164

    248

    2000A

    169

    248

    173

    248

    2500A

    169

    283

    173

    283

    3150A

    169

    308

    173

    308


    Advantage


    High load-bearing capacity


    This type of busway channel adopts steel profile shell, which can carry 70kg of pressure in the center of the 3m span busway, and the center of the plate shell can be shifted by no more than 5mm when the temperature changes non-uniformly.


    Long fire resistance time


    Fire-resistant series busways are divided into NHCCX, NHKMC1 and NHKMC2 according to the structure type and the form of fire-resistant insulation treatment, and their corresponding fire-resistant limits under energized conditions are shown in the table.


    Model

    Structure form

    Fire resistance limit(min)

    Fire-resistant temperature(℃)

    Applications

    NHCCX

    Dense

    60

    850

    Normal power supply

    Firefighting power supply

    NHKMC1

    Air type

    60

    900

    Normal power supply

    Firefighting power supply

    NHKMC2

    Air type

    120

    1050

    Firefighting power supply