Scope Of Application
High-Rise Building
Air-type bus duct is suitable for the power supply of high-rise buildings. Due to its characteristics of miniaturization, high efficiency and energy saving, it can meet the power needs of high-rise buildings.
Large Factory
For the power supply of large factories, traditional cables and busbars are often difficult to meet the demand. At this time, air-type bus trunking can be used for power transmission to reduce transmission costs.
Losses And Safety Risks
Other Places
Air bus duct is also suitable for other places where power transmission is required, such as airports, overhead passages, etc.
Summarize
Air bus duct is a new type of power transmission equipment. It has the advantages of safety, reliability, high efficiency and energy saving. It has a wide range of applications in the power supply of high-rise buildings, large factories and other places.
Extremely Safe And Reliable
A. Using separated air insulation type, the safe clearance distance and creepage distance between phases are much larger than the standard requirements.
B. The internal insulation parts are made of high-strength epoxy resin, which improves the vibration resistance and thermal stability of the bus duct.
Bus ducts of all current levels use unified cover plates, which have a high degree of standardization, strong interchangeability, and convenient variable capacity interfaces.
The Main Technical Parameters
Part Name |
Maximum allowable temperature rise (K) |
Connection terminal |
60K |
Metal shell |
30K |
Insulating surface |
40K |
Rated current(A) |
Busbar specifications for each phase (mm) |
100 |
3X30 |
250 |
4X40 |
400 |
6X40 |
630 |
6X50 |
800 |
6X60 |
1000 |
6X80 |
1250 |
6X100 |
1600 |
6X140 |
2000 |
BX140 |
2500 |
BX175 |
3150 |
BX200 |
4000 |
2-8X140 |
5000 |
2-8X175 |
Selection And Drawings
The connection of the bus duct is shown in the figure.
RTCKX8-2A
High-Rise Building
The air busbar measure is suitable for the power supply of high-rise buildings. Due to its characteristics of miniaturization, high efficiency and energy saving, it can meet the power needs of high-rise buildings.
Large Factory
For the power supply of large factories, traditional cables and busbars are often difficult to meet the demand. At this time, air-type bus trunking can be used for power transmission to reduce transmission costs.
Losses And Safety Risks
Other Places
Air bus duct is also suitable for other places where power transmission is required, such as airports, overhead passages, etc.
Summarize
Air bus duct is a new type of power transmission equipment. It has the advantages of safety, reliability, high efficiency and energy saving. It has a wide range of applications in the power supply of high-rise buildings, large factories and other places.
Structural Features
Shell Features
The shell of this series of bus ducts is made of bent plates, with small size and exquisite appearance; It greatly improves the sub-load capacity. The installation is extremely convenient and adopts the docking installation method, making the motherboard. The wire duct is very convenient and flexible during the installation process, which greatly saves installation time.
Extremely Safe And Reliable
A. Using separated air insulation type, the safe clearance distance and creepage distance between phases are much larger than the standard requirements.
B. The internal insulation parts are made of high-strength epoxy resin, which improves the vibration resistance and thermal stability of the bus duct.
High Degree Of Standardization
Bus ducts of all current levels use unified cover plates, which have a high degree of standardization, strong interchangeability, and convenient variable capacity interfaces.
The main technical parameters
Conductive parts |
Maximum allowable temperature rise (K) |
Shell |
30 |
Insulating material surface |
30 |
Busbar to busbar connection |
60 |
The connection between the plug-in box plug and the busbar |
60 |
Rated current(A) |
Four wire system |
Five-wire system |
W(mm) |
H(mm) |
Weight(kg/m) |
W(mm) |
H(mm) |
Weight(kg/m) |
200 |
152 |
89 |
16.4 |
171 |
89 |
19.6 |
250 |
152 |
84 |
18.2 |
171 |
84 |
21.5 |
400 |
152 |
94 |
20.3 |
171 |
94 |
23.6 |
630 |
152 |
104 |
22.4 |
171 |
104 |
24.9 |
800 |
152 |
119 |
25.6 |
171 |
119 |
28.2 |
1000 |
152 |
134 |
28.8 |
171 |
134 |
32.4 |
1250 |
152 |
169 |
36.5 |
171 |
169 |
39.1 |
1600 |
152 |
189 |
47.1 |
171 |
189 |
51.8 |
2000 |
152 |
224 |
56 |
171 |
224 |
61.2 |
2500 |
152 |
334 |
68.8 |
171 |
334 |
75.7 |
3150 |
152 |
374 |
89.6 |
171 |
374 |
97.5 |
4000 |
152 |
444 |
108.5 |
171 |
444 |
115.8 |
Due to the unique design style and reasonable structure of RTCKX8-2A high-strength closed bus duct, it combines air type and intensive type. It is unique among domestic bus duct products because of its significantly superior mechanical properties and The excellent electrical performance makes it widely used in power distribution rooms, basements, and vertical sections in modern high-rise buildings, large factories, substations, power plants and other power supply places such as electric power, petroleum, chemicals, transportation, and civil aviation.
Busbar functional unit code table
Code name |
Name |
Code name |
Name |
A |
Ordinary bus |
P |
Expansion joint |
S |
Starting bus |
BY |
Transformer connector |
Z |
Terminal cover |
BX |
Adjustment joint |
LS |
L-shaped horizontal joint |
SC |
Cross vertical joint |
LC |
L-shaped vertical joint |
ZS |
Type B horizontal joint |
TS |
T-shaped horizontal joint |
ZC |
Z type vertical joint |
TC |
T-type vertical joint |
SH |
Starting terminal box |
Selection And Drawings
● The bus duct adopts a high-strength fully enclosed structure with a protection level of up to IP30.
● The number of plug-and-pull times between the bus duct plug-in box and the bus duct shall not be less than 200 times.
● The cross-sectional dimensions and weight per meter of the bus duct are shown in the figure and table below.

RTCKX8-2A high-strength closed bus duct structure