Leave Your Message
6300A QBJGM Insulated Pipe Medium Voltage Busway

Medium Voltage Busway

6300A QBJGM Insulated Pipe Medium Voltage Busway

Product Details:

Place of Origin: CHINA
Certification: KEMA,ASTA,CE,GOST-R,CEDIT,TUV
Model Number: Q(B)JGM

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Price: Negotiable
Packaging Details: Standard package
Delivery Time: 20 working days after confirmation of all technical data and advance payment
Supply Ability: 300 Pieces per Month

    product detail

    6300A QBJGM Insulated Pipe Medium Voltage Busway

    Description

    Conductor Type: Cu Pipe / Al Pipe Rated Current: 630A--6300A
    Frequency: 50Hz/60Hz Rated Voltage: 3.6-40.5KV
    IP: IP65 Product Series: Semic Insulated / Insulated
    Design Criteria: DL 1658 AND GB/T 8349 Product Type: Insulate Pipe Busduct
    High Light: QBJGM Medium Voltage Busway, QBJGM Insulate pipe busduct, 6300A Medium Voltage Busway

    Q ( B ) JGM insulated pipe busway , Insulate pipe busduct

     

    To prevent accidental damage to internal shielding and primary insulation during manufacturing.
    12 related patents designed.Prevent the introduction of external impurities between the main insulation layer and the inner shield, as well as the outer shield.
    The internal and external shielding is closely combined with the main insulation layer, which improves the performance of partial discharge resistance and in the fight aganist wear.
    The insulation material is made of high quality ethylene propylene diene diene rubber (EPDM), which not only has excellent electrical insulation performance and corona resistance, but also has aging resistance and corrosion resistance.
    EPDM (ethylene propylene diene ternary rubber) adding with a variety of compounding agents, after being thoroughly mixed, extruded on a tubular conductor, and then heated and vulcanized.

    Standards IEC364-5-54/GB/T8349-2000/JB/T9639-1999
    Ambient  
    Relative humidity   Daily averages ≤ 95%. Monthly average ≤ 90%
    IP   IP40, IP54
    Rated voltage kV 3.15 6.3 10.5 35
    Max operating voltage kV 3.6 7.2 12 40.5
    Insulation level kV 25/40 32/60 42/75 100/185
    Rated frequency Hz 50(60)
    Rated operating current   Dimension (W×H)(mm×mm)
    1000-3000 A I 750×400 II 850×350 I 900×560 II 1060×460 I 900×560 II 1060×460 I 1500×920 II 1800×880
    3500 A I 750×440 II 850×480 I 900×560 II 1060×460 I 900×560 II 1060×460  
    4000 A I 750×440 II 850×480 I 900×560 II 1060×460 I 900×560 II 1060×460  
    4500 A I 750×440 I 1000×560 I 1000×560  
    5000 A I 1350×500 I 1500×600 I 1500×600  
    6300-6800 A I 1350×500 I 1500×600 I 1500×600  

    Q(B)JGM Insulation pipe busway is with tubular conductor. The inside diameter air channel can form hot air convection naturally with good dissipation (the pressure difference between indoor and outdoor can form hot air convection naturally).